- The currenttransformersare in accordance with GB20840.2-2014 andIEC60044-1 standards
- Rated insulation level:12/42/75kV
- Rated secondarycurrent:5A or 1A
- Rated frequency:50Hz or 60Hz
- Ambient temperature:-5℃~+40℃

Â
Rated primary current(A) |
1s thermal current(kA) |
Rated dynamic current(kA |
Accuracy classes combination |
Rated secondary output (VA) |
Surface Creepage Distance(mm) |
Weight (kg) |
|||
0.2,0.2S |
0.5,0.5S |
10P10 |
10P15 |
||||||
5 |
0.75 |
1.8 |
0.2S/10P 0.2/10P 0.5/10P 0.5S/10P 0.2S/0.2 0.2S/0.5 0.2/0.5 |
10 |
10 |
15 |
15 |
245 |
21/23 |
10 |
1.5 |
3.75 |
|||||||
15 |
2 |
5 |
|||||||
20,25 |
3 |
7.5 |
|||||||
30 |
5 |
12.5 |
|||||||
40 |
6.3 |
15.8 |
|||||||
50,60 |
8 |
20 |
|||||||
75 |
12.5 |
31 |
|||||||
100 |
15 |
37.5 |
|||||||
150 |
30 |
75 |
|||||||
200,250 |
45 |
112.5 |
|||||||
300 |
|||||||||
400 |
|||||||||
500 |
|||||||||
600 |
63 |
130 |
|||||||
750,800 |
|||||||||
1000 |
|||||||||
1200,1250 |
80 |
160 |
|||||||
1500 |
|||||||||
2000 |
|||||||||
2500 |
|||||||||
3000 |
|||||||||
3150 |
Â



The LZZBJ9-10A1 is a indoor single-phase current transformer (CT) used in electrical power systems for measuring alternating current (AC). Current transformers are essential components in the energy sector, particularly in high-voltage applications, as they provide a scaled-down current that can be used for metering, protection, and control without directly connecting high-voltage circuits to low-voltage measurement devices.
Â
Â
· High Accuracy: Designed to provide accurate current measurement, crucial for protection and metering in electrical systems.
· Insulation: Epoxy resin casting insulation materials ensure safety and reliability in high-voltage applications.
· Compact Design: Compact and robust design allows for easy installation and integration into various electrical systems.
· Durability: Built to withstand harsh environmental conditions and mechanical stresses.
· Mounting: Designed for easy installation in switchgear, substations, and other electrical distribution systems.
ÂÂ
- Metering: Used in electrical metering systems to provide accurate measurements of current for billing and monitoring purposes.
- Protection: Works in conjunction with protective relays to detect faults and abnormal conditions in the power system, facilitating timely disconnection to prevent damage.
- Control: Provides current feedback to control systems for efficient power distribution and management.