TitleProduct

Madagas Gas Solenoid Valve

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2021-04-11 08:09

  • Browse the number:

    267

Send an inquiries

Company Profile

Zhejiang Sanhao Intelligent Technology Co., Ltd

By certification [File Integrity]

Contact:zhejiangsanhao(Mr.)  

Email:

Telephone:

Phone:

Area:Beijing

Address:Beijing

Website:http://www.madagas.net/ http://zhejiangsanhao.ycspsd.com/

PRODUCT DETAILS

Madagas Gas Solenoid Valve

MVD/5


Technical Description

The MVD/5 series safety solenoid valves are single-stage automatic shut-off valves that meet the requirements of EN 161 for gas burners and gas equipment.

- Max. operating pressure up to 200, 360 or 500 mbar (20, 36 or 50 kPa)

- MVD: fast opening

- Main volume adjustable(MVD/MVDLE)


Gas solenoid valves at home and abroad are divided into three categories in principle

One, direct acting gas solenoid valve: electromagnetic coil electromagnetic force to close the piece from the seat, gas solenoid valve working principle: when energized.Valve open;Power, electromagnetic force dissipation, the spring to close the pressure on the seat, the valve closed.But the diameter is generally not more than 25mm solenoid valve features: vacuum, negative pressure, zero pressure can work normally.


Two, spread the direct acting gas solenoid valve: when there is no pressure difference between the inlet and the inlet, the working principle of the gas solenoid valve: a direct acting and pilot type combined principle.After the power, the electromagnetic force directly to the pilot valve and the main valve closed parts in turn up, the valve opened.When the inlet and outlet to start the differential pressure, after the power, the electromagnetic force pilot valve, the main valve chamber pressure rise, the pressure falls on the chamber, so as to use the differential pressure to push the main valve upward;Power, the pilot valve using spring force or medium pressure to push the sealing parts, moving down, so that the valve closed.But the power is larger, solenoid valve features: zero pressure difference or vacuum, high pressure can also be * action.Request required horizontal device.


Three, pilot gas solenoid valve: gas solenoid valve to open the pilot hole, gas solenoid valve working principle: when energized.The pressure of the upper chamber drops rapidly, and the pressure difference of the upper, lower and higher is formed around the sealing part. The fluid pressure pushes the sealing part upward, and the valve opens;Power, the spring force to the pilot hole closed, the inlet pressure through the bypass hole agile chamber in the close valve around the formation of low and high pressure difference, fluid pressure to push the closed parts move down, close the valve. Can be installed at will (to be customized) but must meet fluid differential pressure conditions.


MVD/5

Madagas Gas Solenoid Valve, normally when closed, fast opening, fast closing, manual limitation of flowing gas volume by adjusting main volume.


Specifications

Nominal diameters

Pipe thread as per ISO 7/1, Rp

Flange

DN15

Rp1/2

Connection flange (PN 16) as per DIN EN 1092-1

Max. operating pressure

360 mbar (36 kPa) or up to 500 mbar (50 kPa) - refer to type overview

Solenoid valve

Valve as per EN 161, Class A, Group 2, single-stage mode

Closing time

< 1 s

Opening time

< 1 s

Fast stroke

Adjustable

Main volume adjustment

Manually adjustable on MVD

Materials of gas-conveying parts

Housing: aluminium, steel, brass

Seals: NBR basis

Voltage/frequency

230 V AC (+10 % -15 %); 50-60 Hz - other voltages on request

Solenoids 60E, 61E in 24-28 VDC

external activation of solenoid coils required, see operating and mounting instructions

Rating / power consumption

Refer to type overview

Switch-on duration

100 %

Degree of protection

IP 54, IP 65 on request

Switching rate

MVD…/5: max. 1000/h

MVD 2125/5, MVD 2150/5, MVD 5100/5, MVD 5125/5, MVD 5150/5: max. 20/h

Measuring/ignition gas connection

G 1/4 ISO 118, on both sides in inlet section, additionally G 3/4 on input side, form size DN 40 (flange) upwards

Dirt trap

Sieve installed, mesh width 1 mm

Ambient temperature

-15 ° C to +60 °C

Installation position

Solenoid from vertically upright to horizontally lying

Closed position signal contact

MVD/5 Type K01/1, DIN-tested, mountable on DN 10 - DN 150

Valve proving system

Type VDK 200 A S02, mountable via G 1/4 test connection, Type VPS 504, mountable with adapter up to DN 80


Type

pmax.

DN / Rp

Solenoid-No.

Pmax.

[VA]

I max.

~ (AC)

230 V

Opening time

Dimensions

[mm]

Weight

[kg]

øa

b

c

d

e

f

MVD 205/5

360

Rp 1/2

100

17

0,08

< 1 s

50

80

90

75

113

150

1,00


Operation and assembly instructions

Solenoid valve

One stage operation

Type MVD …/5

Type MVDLE …/5

Nominal diameters

Rp 3/8 – Rp 2 1/2

DN 20 – DN 100



MVD 205/5

Setting the main flow


Changing solenoid MV 205/5

1. Remove dust cap A. 

2. Replace solenoid Note solenoid no. and volt age! 

3. Screw on dust cap A.

We reserve the right to make any changes in the interest of technical progress.

ITALY MADAGAS TECHNOLOGY LIMITED

Telefon +86-133 6276 8518

Telefax 0577-62869980

WeChat public address:renengegou

ch3h@ch3ch.com


http://www.madagas.net/